PAT test pass and fail limits are the numbers that decide whether a portable electrical item goes back to work or comes off site. A pass needs a clean visual inspection plus readings inside the limit for earth continuity, insulation resistance or leakage. This guide explains each limit, what a failure usually means, and how UAE site conditions affect results. If you need the tests carried out, see Tamam Safety’s portable appliance testing in the UAE page.
- A PAT result has two parts: a visual inspection and electrical readings. Failing either one fails the item.
- For Class I items, the earth continuity limit is 0.1 ohm plus the resistance of the supply cord’s earth conductor, so long leads get a slightly higher limit.
- Insulation resistance is commonly judged at a 1 megohm minimum for Class I and 2 megohm for Class II, tested at 500 V DC. Some electronic items need a leakage test instead.
- A failed item is repaired and retested, or removed from service. It is never retested until it happens to pass.
- We found no UAE rule that sets these limits, so most sites follow IET and HSE guidance and the requirements of their client or insurer.
What do PAT test pass and fail limits actually mean?
A PAT limit is the threshold a reading must meet for an appliance to be judged safe for continued use. If a reading falls outside its limit, or the item is visibly damaged, the result is a fail. The limit depends on the equipment class and the test applied.
Portable appliance testing combines a close visual inspection with electrical tests. Tamam Safety’s own description of the work lists visual inspection, insulation resistance, earth continuity, polarity and functional checks, followed by labelling with the test date, next due date, identification number and result. The limits give that label a meaning.
Two points are easy to miss. First, the visual inspection comes first and can fail an item before any meter is connected. Second, limits are not universal constants. They vary with equipment class, cord length and test voltage, and many testers let the user configure them.
The wider context matters too. HSE guidance HSG107 describes a three-tier approach: user checks, formal visual inspection by a competent person, and combined inspection and testing. Electrical readings are one layer in that system, not a replacement for the others.
Class I and Class II: why the class changes the limit
A Class I appliance relies on an earth connection for protection, so its earth path must be tested. Many drills, kettles, heaters and metal-cased tools fall into this group. A Class II appliance has double or reinforced insulation and no earth conductor, so the earth test does not apply and the insulation test carries more weight.
Some items, such as computers and laptop chargers, behave differently again. Their electronics can be affected by a 500 V DC test, which is why the leakage method exists. We return to this below.
What is the earth continuity limit and why does the cord matter?
The IET guidance sets the earth continuity limit at 0.1 ohm for appliances without a supply cord. For cord-connected appliances the limit is 0.1 ohm plus the resistance of the cord’s protective conductor. A reading above that figure fails because the fault path may be too weak.
The earth conductor must carry fault current long enough for the protective device to operate. If resistance is high, a fault can leave the metal case live. That is why even a small excess matters on a Class I item.
Take an illustrative case. A heater lead has an earth conductor that measures 0.078 ohm on its own. Using the formula, the limit for the whole appliance is 0.178 ohm. A reading of 0.15 ohm passes. A reading of 0.40 ohm fails, and the cause is usually in the plug, the terminal or the body connection rather than in the cord itself.
The IET also describes a low-current version of the earth test, around 200 mA or less, for sensitive electronic equipment. It is used where a high test current could damage the item. Check the Code of Practice and your tester’s manual before choosing it.
Tester settings deserve a check. Some instruments default to a fixed limit, for example 0.2 ohm for Class I on one common model, and the user can change it. A tester left on the wrong limit gives a wrong verdict in both directions. Read the IET’s earth continuity test guidance before configuring yours.
Reading the number in context
A borderline earth reading is a prompt to flex the cord during the test. If the number jumps as you bend the cable near the plug or the appliance entry, the conductor is damaged inside the sheath. That is a repair or replacement case, even if the static reading briefly passes.
What insulation resistance reading passes a PAT test?
Class I equipment is commonly judged against a minimum of 1 megohm, tested at 500 V DC, as set out in IET guidance. Class II equipment is commonly judged against 2 megohm, as shown in tester manuals. A reading below the minimum fails, because current may be leaking through damaged or contaminated insulation.
The insulation test checks that live parts are separated from touchable metal. Dust, moisture, cracked sheathing and overheated insulation all lower the reading. A high reading means the separation is intact.
Two caveats apply. Appliances with heating elements, such as kettles and fan heaters, often read lower because elements absorb moisture and have a different design. Equipment with surge protection or mains filters can also read oddly. These cases need the Code of Practice and the manufacturer’s information, not a quick pass or fail.
The 2 megohm figure for Class II comes from tester manufacturers and training material, not from the IET text we could read. Treat it as a common setting and confirm it against your copy of the Code.
When is a leakage current test used instead?
The IET describes leakage current testing as an alternative when the insulation test cannot be carried out or gives doubtful results. It measures current flowing through the protective conductor or touchable parts while the item is powered. It is mainly used for electronic equipment that a 500 V DC test could damage.
The IET leakage guidance lists limits of 0.75 mA for portable or hand-held Class I equipment, 3.5 mA for other Class I equipment and 0.25 mA for Class II equipment. These are small currents, so the item must be tested with the correct connection and a tester suited to the method.
Equipment with a high protective conductor current, such as banks of computers or some IT racks, needs separate handling. Each item may pass individually while a shared extension lead carries the sum. See the IET’s guidance on equipment with high protective conductor current for the approach.
| Test | Typical pass reading | Applies to | Common cause of a fail |
|---|---|---|---|
| Visual inspection | No damage, correct fuse, plug and cord sound | All items | Cut or crushed cord, cracked plug, burn marks |
| Earth continuity | Below 0.1 ohm plus cord earth resistance | Class I | Loose terminal, damaged conductor, poor plug |
| Insulation resistance (500 V DC) | At least 1 megohm (Class I), 2 megohm (Class II) as commonly set | Class I and II | Moisture, dust, aged or damaged insulation |
| Leakage current | Up to 0.75 mA, 3.5 mA or 0.25 mA by category | Electronic items where insulation test is unsuitable | Filter capacitors, damaged insulation, high-load groups |
| Polarity and function | Correct wiring and normal operation | Leads, extension reels, appliances | Crossed conductors, faulty switch, wrong fuse |
How do you read a PAT result sheet step by step?
Read a result sheet from the visual line downward, then match each electrical reading to its limit for that item. Any failed line fails the whole appliance. Note the class, the test type and the limit used, then decide on repair, removal or retest.
- Confirm the identity — match the asset ID on the sheet to the label on the item and its location, so the record follows the right appliance.
- Check the class — confirm Class I or Class II, because the limits and tests differ.
- Read the visual result — look for notes on the cord, plug, fuse rating, casing and signs of overheating.
- Compare each reading with its limit — for earth continuity, include the cord allowance; for insulation, note the test voltage.
- Look at the limits the tester used — confirm they match your site’s chosen Code of Practice settings.
- Flag every borderline reading — readings close to a limit may deserve a retest or an earlier review date.
- Assign an action — pass, repair, remove from service or retest.
- Update the register — record the result, the action, who took it and the next due date.
What should happen after a PAT test fail?
A failed item is taken out of use immediately and labelled so nobody plugs it back in. A competent person then decides whether it can be repaired. After repair it is retested and passes only if every reading meets the limit. Otherwise it is scrapped.
The table below gives a practical decision guide. It is general guidance, not a legal schedule, and your own risk assessment still decides the final action.
| Finding | Likely meaning | Next step |
|---|---|---|
| Clean visual, all readings inside limits | Item is in a safe condition at the time of test | Pass. Label and set the next review date. |
| Wrong or oversized fuse, loose plug screw | Simple fault, fixed without special parts | Repair, then retest and record both results. |
| Earth reading above limit | Poor connection or damaged conductor | Remove from service. Repair plug or cord if possible, retest. |
| Low insulation reading | Moisture, contamination or damaged insulation | Remove from service. Dry and retest only if cause is clear; otherwise scrap. |
| Cut, crushed or burnt cable | Mechanical or heat damage | Remove from service. Replace the cord or the item. |
| Reading changes when cord is flexed | Internal conductor damage | Remove from service and replace the lead. |
| Borderline reading, no visible fault | Item is ageing or near its limit | Retest after cleaning the contacts, and shorten the review interval. |
Why a retest is not a second chance
Retesting is valid after a fix, not as a way to chase a pass. Repeating a test on an unchanged item until the number improves records luck rather than safety. Always note what changed between the fail and the retest.
How do UAE heat, dust and humidity change PAT results?
UAE conditions can lower insulation readings and damage cords faster than in a cool indoor office. Humidity and coastal air add moisture, dust builds up inside tools, and heat softens cord sheathing. These factors make some items fail earlier and justify shorter review intervals for site equipment.
Construction and industrial sites are the hardest on portable equipment. Extension reels are dragged across sand, crushed by vehicles and left in direct sun. Power tools collect abrasive dust in vents and switches. Cord sheathing that has spent summers outdoors can harden and crack near the plug.
Food, hospitality and marine settings add their own stresses. Kitchens bring steam, grease and frequent cleaning. Marine and coastal sites bring salt, which promotes corrosion of terminals and earth connections. A reading that passes in a dry store may fail on a humid morning for the same appliance.
Thermal imaging can complement PAT where overheating is suspected in distribution boards or heavily loaded leads. Tamam Safety offers an NDT thermal imaging service for that kind of follow-up, and a calibration service supports instrument accuracy. Sites with exposed structures may also review their lightning protection system, since surges are one source of electrical damage.
Do UAE rules set the limits?
We found no official UAE or Dubai rule that prescribes portable appliance test limits or intervals. Dubai Municipality has a Local Order No. 10 of 2003, amended in 2016, on technical conditions for electrical equipment in Dubai, and DEWA publishes regulations for electrical installations. Neither is a portable appliance test schedule that we could confirm.
Treat the IET and HSE material as a recognised reference, not as UAE law. Ask your client, insurer, landlord or authority which limits and records they expect, and write the answer into your site procedure.
Common mistakes
- Using one limit for everything — a Class II insulation limit applied to a Class I heater, or a fixed earth limit applied to a 30 metre reel, gives wrong verdicts.
- Ignoring cord length — the earth limit grows with the resistance of the cord’s earth conductor, so long leads need the correct allowance.
- Retesting until it passes — a pass without a repair says nothing about safety.
- Applying 500 V DC to sensitive electronics — guidance says it can damage some equipment, so use the leakage method where suitable.
- Skipping the visual inspection — damage to a plug, cord entry or casing often shows before any meter does.
- Leaving failed items on site — an unlabelled fail gets plugged back in. Quarantine it and tag it.
- Setting one interval for all areas — an office desk lamp and a site extension reel do not carry the same risk.
- Not recording the limits used — a result without its limit cannot be audited later.
Terms explained
- Class I appliance is a product that relies on a protective earth connection as well as basic insulation.
- Class II appliance is a product with double or reinforced insulation and no earth conductor.
- Earth continuity is a measure of the resistance of the protective earth path from the plug to the exposed metal.
- Insulation resistance is the resistance between live conductors and touchable metal, measured with a high test voltage.
- Leakage current is the small current that flows through the protective conductor or touchable parts during normal operation.
- Competent person is someone with the training, equipment and experience to judge faults and interpret readings.
- Formal visual inspection is a recorded check for damage and wear, usually by a trained employee, without electrical test equipment.
How does portable appliance testing apply across all seven emirates?
The same limits and decision steps apply in every emirate, because they follow the equipment and not the location. What changes is the site environment and the equipment mix. Tamam Safety’s PAT page describes work across the UAE, and the notes below show where each emirate’s conditions affect readings.
For wider background on testing appliances and what Tamam Safety checks, the earlier post on PAT testing in Dubai covers the basics, and the post on pre-use checks versus thorough examination for lifting equipment shows the same user-check-versus-formal-test thinking applied to lifting equipment.
Frequently Asked Questions
An item passes when the visual inspection finds no damage and every electrical reading sits inside the limit set for its class and test type. It fails if any single reading, or any visible defect, falls outside the limit. One failed reading is enough to withdraw the item, even if the others look fine.
For a Class I appliance, the guidance limit is 0.1 ohm plus the resistance of the supply cord’s own earth conductor. A reading above that limit fails. Your tester may use a fixed default instead, so check its configured limit and the current Code of Practice before relying on one number.
Class I equipment is commonly assessed against a 1 megohm minimum at 500 V DC, and Class II against 2 megohm, as shown in tester manuals. Anything below the minimum fails. A low reading on an item with a heating element or surge protection needs a second look before it is condemned.
Not without finding the cause. A fail means something is wrong, such as damaged insulation, a loose earth conductor or moisture. Repeating the test until a pass appears hides the fault. Repair the item, then retest it and record both results, or remove it from service.
We did not find an official UAE or Dubai rule that prescribes portable appliance test limits or intervals. Many clients and insurers still require records, and the IET and HSE guidance is widely used as a reference. Confirm what your client, landlord or authority expects before setting a schedule.
A new lead can fail from a loose terminal, a poorly crimped plug, a damaged conductor or a tester lead that was not connected firmly. Long reels also carry more cord resistance, so the limit must account for length. Re-seat the connections, retest, and reject the lead if it still fails.
The current IET Code of Practice treats the interval as a risk decision rather than a fixed rule. Hot, dusty or heavily handled equipment such as site tools and extension reels usually needs checking more often than desktop office items. Review the interval after each round of results.
A competent person should review them, meaning someone with the training and equipment to judge faults and interpret readings. Failed items should not return to use on the strength of a verbal assurance. Keep the result sheet, repair note and retest result together as one record.